FinanceEngineering ToolboxGen Set RatingsGen Set SpecificationsGen Set FoundationsGen Set Rooms & EnclosuresGen Set VentilationGen Set NoiseGen Set Starting SystemsGen Set Cooling SystemsGen Set Exhaust SystemsGen Set Engine GovernorsGen Set FuelsGen Set SizingGen Set Motor StartingOther Generator Technical ConsiderationsGen Set TestingAutomatic Transfer Switches

Understanding Generator Set Noise

Effectively controlling sound levels produced by operating generator sets is becoming a higher priority. Numerous governmental agencies are enacting noise ordinances, aiming to cut noise pollution. This directly affects gen set installation design.

Understanding Noise

Noises are quantified by their sound pressure, and most commonly measured in decibel levels heard by humans, noted as dB(A).

The relationship between decibel level is logarithmic. In terms of loudness, doubling the sound pressure roughly equates to a 6 dB(A) increase; doubling the distance from the noise source reduces the sound level by half. Typical noise level ratings are noted in Table 2.

Table 1 - Typical noise levels

Jet engine 160
Riveting 140
Punch press 120
City traffic 100
Busy office 80
Normal speech 60
Quiet suburb 40
Whisper 20
Threshold of hearing 0

Loudness is also affected by the frequency of sound, but to a much less degree than sound pressure. It's important to note that decibel levels will not necessarily equal the summation of each noise source. For example, two gen sets operating do not produce a 2X decibel level, but increase total sound level by 3 dB(A).

Controlling Gen Set Noise

Noise from gen sets can be effectively controlled with good engineering practices at installation. Table 3 estimates the relative effectiveness of various sound barriers.

Table 2 - Approximate sound level reduction dB(A)

Original machine 0
Vibration Isolators 2
Baffle 5
Absorption material only 5
Rigid sealed enclosure 15 - 20
Enclosures and isolators 25 - 30
Enclosure, absorption, and isolators 35 - 40
Double walled enclosure, absorption, and isolators 60 - 80

Designers must consider two noise sources— the actual mechanical noise of the gen set and the exhaust noise. Exhaust silencers can be specified by the following site descriptions.

  • Industrial: Suitable where background noise is relatively high.
  • Semi-industrial: Suitable for standby systems or environments where complete silencing is not required.
  • Residential: Suitable for use where moderate background noise is permissible.
  • Semi-residential: High noise attenuation with low background noise.
  • Critical: Extreme noise attenuation with low background noise.

Attenuating mechanical noise can be completed with a combination of sound dampening design and by isolating vibration produced by the operating gen set. Table 2 shows the sound level reduction possible. Completely sealed enclosures are included as a reference, but openings for piping, airflow, etc. will adversely affect these reduction levels.

We have aided in the design and installation of generator sets, and can offer you the expertise and software, such as EPG Designer, to help you control noise emissions from gen sets. If you need assistance in this area, please call us. We would be glad to help.

 

YOUR TOTAL SOLUTIONS PROVIDER

MacAllister Power Systems has 7 convenient locations throughout Indiana:
Fort Wayne, Indianapolis (HQ), Indianapolis - Brookville Rd (Blue Bird Bus), Lafayette, South Bend, Terre Haute, and Washington.

Headquarters: 7575 E 30th St, Indianapolis, IN 46219
Phone: (317) 545-2151  Toll Free: (800) 382-1896  Online: Contact Us