Product Specs
Generator Set Specifications
- Standby Rating
- 1750 ekW
- Prime Power Rating
- 1600 ekW
- Emissions/Fuel Strategy
- Low Fuel Consumption
- Voltage
- 380 to 480 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Mission Critical, Prime, Continuous
- Maximum Rating
- 1750 ekW
- Minimum Rating
- 1450 ekW
Engine Specifications
- Engine Model
- 3516 TA, V-16, 4-Stroke Water-Cooled Diesel
- Bore
- 6.69 in
- Stroke
- 7.48 in
- Displacement
- 4210.64 in³
- Compression Ratio
- 13.5:1
- Aspiration
- TA
- Fuel System
- Mechanical unit injection
- Governor Type
- Woodward
Generator Set Dimensions
- Length - Maximum
- 234.4 in
- Width - Maximum
- 90 in
- Height - Maximum
- 94.9 in
- Dry Weight - Genset (maximum)
- 28840 lb
Standard Equipment
-
- Air Cleaner
-
- Single element with service indicator
-
- Starting
-
- Heavy duty electric starter(s)
-
- Cooling
-
- Standard Ambient Radiator
-
- Mounting System
-
- Rails
-
- Controller
-
- EMCP 4.2B
-
- Telematics
-
- Ethernet
-
- Alternator
-
- Random Wound
- Internal Excitation (IE)
-
- Power Termination
-
- Busbar
Attachments
-
- Air Cleaner
-
- Dual element with service indicator
-
- Starting
-
- Dual electric starters
- Standard batteries
- Oversized batteries
- Battery charger - 10A
- Battery charger - 20A
- Battery charger - 35A
- Air starter(s)
- Jacket water heater
-
- Cooling
-
- No Radiator
- High Ambient Radiator
-
- Muffler
-
- Industrial grade (15 dB)
-
- Mounting System
-
- Rubber
- Spring vibration Isolators
- Seismic rated vibration isolators
-
- Controller
-
- EMCP 4.3
- EMCP 4.4
-
- Controller Attachments
-
- Local annunciator module
- Remote annuciator module
- Expansion I/O module
- Remote monitoring software
-
- Telematics
-
- Cellular
-
- Extended Service Terms
-
- 2 year (Prime)
- 3 year
- 5 year
- 10 year
-
- Extended Service Coverage
-
- Silver
- Gold
- Platinum
- Platinum plus
-
- Alternator
-
- Permanent Magnet (PM) Excitation
-
- Alternator Temperature Rise (over 40°c Ambient)
-
- 80°C
- 105°C
- 125°C
- 150°C
-
- Alternator Output Voltage
-
- 380V
- 480V
-
- Alternator Attachments
-
- Anti-condensation space heater
- Stator and bearing temperature monitoring and protection
-
- Power Termination
-
- Circuit breaker
-
- Circuit Breaker
-
- 1600A
- 2000A
- 2500A
- 3200A
- 4000A
- Electrically operated
-
- Trip Unit
-
- LSI
- LSI-G
- LSIG-P
-
- Ancilliary Equipment
-
- Automatic transfer switch (ATS)
- Paralleling switchgear
- Paralleling controls