Product Specs
Generator Set Specifications
- Maximum Rating
- 500 ekW
- Minimum Rating
- 455 ekW
- Emissions/Fuel Strategy
- U.S. EPA Tier 4 Final
- Voltage
- 480 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Prime
Engine Specifications
- Engine Model
- C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
- Bore
- 1455.7 in
- Stroke
- 7.2 in
- Displacement
- 1106.4 in³
- Compression Ratio
- 14.5:1
- Aspiration
- Air to Air Aftercooled
- Fuel System
- Electronic unit injection
- Governor Type
- Adem™A4
Standard Equipment
-
- Air Inlet
-
- Air cleaner
-
- Exhaust System
-
- Exhaust manifold - dry
-
- Cooling
-
- Package mounted radiator
-
- Fuel System
-
- Fuel cooler
- Engine fuel transfer pump
- Primary fuel filter w/integral water separator and secondary filter
- Fuel priming pump
- Flexible fuel lines
-
- Exhaust
-
- Exhaust flange outlet
-
- Fuel
-
- Primary fuel filter with integral water separator
- Fuel priming pump
- Secondary fuel filters
-
- Generator
-
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
- Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
-
- Power Termination
-
- Busbar
-
- Lube System
-
- Oil filter and dipstick
- Lubricating oil
- Oil drain lines with valve; piped to edge of base
- Fumes disposal, piped to front of radiator
- Oil cooler
-
- Control Panel
-
- GCCP Genset Controller
-
- Mounting
-
- Rubber vibration isolators
-
- Protection System
-
- Safety shutoffs for: Higher water temperature - Overspeed - Low oil pressure
-
- Cooling System
-
- Thermostats and housing, full open temperature 92 deg C (198 deg F)
- Coolant level sensor
- Coolant level sight gauge
- Fan and belt guards
- Jacket water pump, gear driven, centrifugal
- Coolant drain line with valve; terminated on edge of base
- Caterpillar extended life coolant
-
- Starting/charging
-
- 24V, 45 Amp Charging alternator
- 24 Volt electric starting motor
- 24 volt starting motor
- Batteries
-
- General
-
- Paint - Caterpillar yellow except rails and radiators gloss black
- Paint, Caterpillar yellow
- Operation and maintenance manual pack and OMM storage compartment
- Parts book
- Vibration damper
-
- Control System
-
- Local annunciator
- Programmable Input / Output: 2 programmable digital inputs - 2 programmable relay outputs (Form A) - 2 programmable relay outputs (Form C)
- Suitable for use as service equipment label
- Separation plate
- Control panel mounting location
- Breaker box mounting location
- Optional external analog input
- Remote annunciators
- GCCP 1.2
- Communications: Customer data link (RS485 Modbus RTu) - Serial annunciator module data link for local and remote annunciator IVR - Integrated Voltage Regulation (Digital) - EM10 Excitation Module
- Controls include: Run/auto/ stop/control - Speed adjust - Voltage adjust - Engine cycle crank - Emergency stop pushbutton
- Digital indication for: rpm - DC volts - operating hours - Oil pressure (psi, kPa or bar) - Coolant temperature (C or F) - Volts (L-L & L-N), frequency (Hz) - Amps (per phase & average) - Power factor (per phase & average) - kW (per phase & average) - kVA (per phase & average) - kVAr (per phase and average) - kW-hr (total) - kVAr-hr (total)
- Programmable protective relaying functions: Generator phase sequence - Over/under voltage (27/59) - Over/under frequency (81 o/u) - Overcurrent (50/51)
- Warning/shutdown with common LED indication of shutdowns for: Low oil pressure - high coolant temperature - Overspeed - Emergency stop - Failure to start (overcrank) - Low coolant temperature - Low coolant level
- Control panel options: Dust proof control panel - volt free contact - Device server - Ground fault relay
-
- Governing System
-
- Cat electronic governor (ADEM A4)
-
- Generator And Attachments
-
- Segregated low voltage (AC/DC) wiring panel
- Brushless, self-excited 2/3 pitch, random wound.
- Insulation Class H and temperature rise
- AREP generator
- CIP - generators
- IP23 Protection
- Power center, IP22 bottom cable entry
-
- Air Inlet System
-
- Single element air filter
- Air cleaner - Heavy duty
- Air cleaner - Single element
-
- Extended Service Coverage
-
- Silver, Gold and Platinum coverage
-
- Circuit Breakers
-
- 3 Pole 100% rated
Attachments
-
- Control System
-
- Ground fault relay
- Dust proof control panel
- Breaker box mounting location
- Volt free contact
- Device server
- Separation plate
- Remote annunciators
- GCCP 1.5
- Local annunciator
- Remote E-stop button
- Optional external analog input
- Control panel mounting
-
- Exhaust
-
- Industrial, residential, critical mufflers
-
- Generator
-
- Anti-condensation heater
- Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
- Oversize and premium generators
-
- Power Termination
-
- Circuit breakers, UL listed
-
- Generators And Attachments
-
- AREP generator
- CIP generators
- Space heater
- Generator mounting and duct plate
-
- Air Inlet System
-
- Single element air filter
- Dual element air cleaner
-
- Certifications
-
- Certificate of Compliance
- IBC Certification wind load
-
- Circuit Breakers
-
- Motorized single circuit breaker
- Neutral bars
- Power cables
- Dual breakers first circuit breaker (CB2) LS/I package mounted
- Current transformers
- Package mounted single circuit breakers
- Dual breakers first circuit breaker (CB1) LS/I package mounted
- Auxiliary contacts
-
- Cooling System
-
- Aftertreatment guard
- Standard radiator
-
- Enclosures
-
- Sound attenuated enclosures
-
- Exhaust System
-
- Flange kits
- Exhaust flexible fittings
-
- Fuel System
-
- 660 gallon base tank
-
- Generator Attachments
-
- Permanent magnet excitation (PMG) generator
-
- Mounting System
-
- Standard base wide
- 5 Gallon spill containment
- Optional CB shroud
- Overfill prevention valve
- Locking fuel fill
-
- Starting / Charging System
-
- Battery disconnect switch
- Jacket water heater
- Shore power control group
- 10 Amp dual Battery charger
-
- Tests
-
- PGS Test report @ 0.8 power factor
- 4 Hour factory test (un-witnessed)
- PGS Test report @ 1.0 power factor
- Generator test report